Installation requirements: The distribution cabinet should be installed upright and firmly, and should not be inverted or skewed. The distance between the bottom of the fixed distribution box and the ground should be between 1.3 meters and 1.5 meters, and the distance between the bottom of the mobile distribution box and the ground should be between 0.6 meters and 1.5 meters.
Power line connection: It is strictly prohibited to connect the power line entering the high-voltage distribution cabinet with a plug.
Switch box setting: Each electrical equipment should have its own dedicated switch box and must meet the requirements of "one machine, one switch, one leakage". It is strictly prohibited to use the same switch to directly control two or more electrical equipment.
Safety measures: The distribution box door should be equipped with a lock, and other temporary electrical equipment should not be hung or plugged in the distribution box and switch box. It is strictly prohibited to place debris inside the switch box.